UNDERGROUND FIRE-FIGHTING SYSTEM WITH HORIZONTAL CENTRIFUGAL PUMPS
Negative suction head fire-fighting system for underground installation with horizontal centrifugal pumps (END-SUCTION), according to UNI EN 12845:2020 standard. The system includes: water storage tank and integrated fire pump room complete with uncovered stairwell with safety rail for access from the outside, and pump compartment separation wall.

TANK AND FIREBOX
- Firebox and stairwell located inside the tank
- Tank material: S235JR carbon steel according to UNI 10025
- Components and accessories according to UNI EN 12845: 2020 and UNI 11292: 2019 fire regulations (see specific section on p. 80). Various options are also available, such as reinforcements to make the system suitable for vehicles and anti-floating devices in the event of groundwater.
- System dimensions as per the following tables. Also available made to measure, and/or modular in dimensions over 100 m3 .
- Access: safety parapet leading to a straight staircase with handrail, compliant with UNI 10803 and UNI 10804 standards and to a single front door made with A1 fire reaction class material.
- Tank painting: internal and external: bitumen epoxy, 120 micron thickness
- Firebox floor: non-slip chequered sheet metal
- There is an inspection pit on the tank for the water side and a pit on the pump side, to extract the pumping units in case of maintenance
Render impianto MF CO-HSUB con esempio applicazione

MF CI-TIU firebox access door detail

MF CI-TIU interior

MF CI-TIU access stairs detail

PUMPING GROUP
Pumping system electrically and hydraulically installed inside the tank in positive suction head installation compliant with the UNI EN 12845:2020 standard in the set-ups with electric and/or motor pumps.

DIMENSION TABLE UNDERGROUND FIRE-FIGHTING SYSTEM WITH HORIZONTAL CENTRIFUGAL PUMPS | MajiFire MF CI-TIU*
| Working capacity(m3) | Ø (mm) | L VS (mm) | L LT from-to (mm) | L S (mm) | L TOT from-to (mm) | Thickness (mm) | Weight from-to ** (q) |
| 10 | 3000 | 3500 | 2500 – 4100 | 2000 | 8000 – 9600 | 6 | 82 – 90 |
| 15 | 3000 | 3500 | 2500 – 4100 | 2500 | 8500 – 10100 | 6 | 83 – 92 |
| 20 | 3000 | 3500 | 2500 – 4100 | 3500 | 9500 – 11100 | 6 | 88 – 96 |
| 25 | 3000 | 3500 | 2500 – 4100 | 4000 | 10000 – 11600 | 6 | 90 – 98 |
| 30 | 3000 | 3500 | 2500 – 4100 | 5000 | 11000 – 12600 | 6 | 94 – 102 |
| 40 | 3000 | 3500 | 2500 – 4100 | 6500 | 12500 – 14100 | 6 | 100 – 109 |
| 50 | 3000 | 3500 | 2500 – 4100 | 8000 | 14000 – 15600 | 6 | 108 – 115 |
| 60 | 3000 | 3500 | 2500 – 4100 | 9000 | 15000 – 16600 | 6 | 112 – 120 |
| 70 | 3000 | 3500 | 2500 – 4100 | 10500 | 16500 – 18100 | 6 | 119 – 127 |
| 72 | 3000 | 3500 | 2500 – 4100 | 11000 | 17000 – 18600 | 6 | 120 – 129 |
| 80 | 3000 | 3500 | 2500 – 4100 | 12000 | 18000 – 19600 | 6 | 125 – 133 |
| 90 | 3000 | 3500 | 2500 – 4100 | 13500 | 19500 – 21100 | 6 | 131 – 140 |
| 100 | 3000 | 3500 | 2500 – 4100 | 15000 | 21000 – 22600 | 6 | 139 – 147 |
* Approximate dimensions to be confirmed upon order
** Empty weight and without pumping group