MF KDN BS

NEGATIVE SUCTION HEAD FIRE-FIGHTING GROUP

Gruppo antincendio soprabattente e sottobattente
Gruppo antincendio soprabattente e sottobattente accessori

TANK
Basin to contain any fuel spills from the diesel tank, included up to 11kW  motor power, as required by the UNI 11292 standard

Gruppo antincendio soprabattente e sottobattente batterie

CLAPET VALVE
A non-return valve that can be inspected is mounted on the delivery of each main pump, so to simplify maintenance.

Gruppo antincendio soprabattente e sottobattente telaio

CONTROL PANELS
All fire-fighting groups include an electrical control panel, according to EN 12845/UNI 10779 for each main pump and an electrical panel for the jockey pump, already connected to the main components (motor, pressure switches, sensor, batteries, etc.).

NEGATIVE SUCTION HEAD FIRE-FIGHTING GROUP

Compact dimensions and modular structure in order to be coupled together (modular design) so as to be able to compose and satisfy all the versions provided for by the EN 12845 standard and facilitate their transport and handling in confined spaces.

Gruppo antincendio soprabattente e sottobattente

TANK
All motor pumps are equipped with a fuel tank dimensioned for 6 hours of operation, as required for the maximum hazard classes according to EN12845 – 10.9.6

CLAPET VALVE
A non-return valve that can be inspected is mounted on the delivery of each main pump, so to simplify maintenance.

CONTROL PANELS 
All fire-fighting groups include an electrical control panel, according to EN 12845/UNI 10779 for each main pump and an electrical panel for the jockey pump, already connected to the main components (motor, pressure switches, sensor, batteries, etc.).

HYDRAULICS
End-suction back pull out normalised horizontal axis centrifugal pump (as required by EN 12845 – 10.1) coupled to an electric or diesel motor by means of a spacer elastic joint protected by safety joint cover.

MOTORS
All the main pump motors are dimensioned in accordance with EN 12845 – 10.1, capable of providing the power absorbed by the pump in any load condition up to NPSH equal to 16 m.c.a.

HIGH QUALITY
Fire-fighting groups designed and manufactured with components that guarantee high quality standards.

“MF KDN BS” COMPACT EN12845 FIRE-FIGHTING GROUP PERFORMANCE

Range of fire-fighting groups with flow rates up to 650m3 /h and heads up to 130 m.

* KDN OVERSIZE : 125-250 / 125-330 / 150-250

RANGE MF KDN BS OVERSIZE

  • Flow rate: up to 650 m3/h
  • Head: up to 130 m

RANGE MF KDN BS NORMALIZZATE

  • Flow rate: up to 400 m3/h
  • Head: up to 120 m

SUCTION HEAD FIRE-FIGHTING GROUP CAPACITY PER MODEL

Group Model
MF KDN BS
P2
Electric[kW]
P2
Diesel[kW]
CAPACITY Q
m3/h0612182430364248546066727884
l/min010020030040050060070080090010001100120013001400
KDN 32-160.1/16137,1
H[m]
323230272110–––––––––
KDN 32-160.1/16947,1363635322616–––––––––
KDN 32-160.1/1775,57,140393937332612––––––––
KDN 32-160/1775,57,1444343424037322823––––––
KDN 32-200.1/1905,57,14544433731218––––––––
KDN 32-200.1/2005,57,152514844362814––––––––
KDN 32-200.1/2075,57,156555348433220––––––––
KDN 32-200/1807,57,14342413936302313–––––––
KDN 32-200/1907,57,1464645444038322518––––––
KDN 32-200/2007,57,1545353504844393220––––––
KDN 32-200/210111158575756555248423628–––––
KDN 32-200/219111165656463615853484032–––––
KDN 32-250/2571515909089887963–––––––––
KDN 40-160/1617,57,1353534343433323129262218–––
KDN 40-160/1771111444443434342414038363431272418
KDN 40-200/20011115050494949494847454238342924–
KDN 40-200/219151561616060595856555214844413631–
KDN 40-250/2301519727272717068666461585448–––
KDN 40-250/24018,51977777776767574716965615650––
KDN 40-250/2603026919191909090898785817875706660
Group Mode
MF KDN BS
P2
Electric[kW]
P2
Diesel[kW]
CAPACITY Q
m3/h012182430364254607284102114120150
l/min02003004005006007009001000120014001700190020002500
KDN 50-160/1611111
H[m]
323434343333333333292419–––
KDN 50-160/17715154242424241414141414038343230–
KDN 50-200/1901515484848484747464543383320–––
KDN 50-200/21018,5195959585858575756555248403428–
KDN 50-200/21922266464646464646362615955484238–
KDN 50-250/2302226707070707069696866625674540––
KDN 50-250/25030378383838383828281807773645753–
KDN 50-250/26337379292929292919191908783766561–
KDN 65-160/1531111292929292929292928272724222114
KDN 65-200/19018,519484848484848484848474542393623
KDN 65-200/2002226535353535353535252525250474434
KDN 65-250/2303026717171717170706969686661585639
KDN 65-250/2503737838383838383838382818077757361
KDN 65-250/2634553939393939393939392919088858474
KDN 65-315/27555531041041041041041031031031021019997959484
KDN 65-315/290757311711711711711711711711711611511411110910799
KDN 65-315/30590110130130130130130130130130129128127126125122115
KDN 65-315/320110110142142142142142142142142142141139138138136131
Group Model
MF KDN BS
P2
Electric[kW]
P2
Diesel[kW]
CAPACITY Q
m3/h042608490120150180210240270300330360390
l/min07001000140015002000250030003500400045005000550060006500
KDN 80-160/1773026
H[m]
4040404039393836332926––––
KDN 80-200/20037375151515151504947423527––––
KDN 80-250/2405573767676767675747166594621–––
KDN 80-250/26075110909090909089888783777062–––
KDN 80-250/2709011098989898989695949188827465––
KDN 80-315/29011011011411411411411411311210910797938070––
KDN 100-200/2005553525252525251515049484442393632
KDN 100-200/2197573646464646464636261605856535047
KDN 100-250/24090110747474747473737170706864595650
KDN 100-250/260110110898989898989888887868482797670
KDN 125-250/23590110727272727270707068666462605754
KDN 125-250/264160145979797979797969695949493918987
KDN 125-330/300160164123123123123123122121121120119118117115111107

MF KDN BS | Negative suction head installation

(P.to 10.6.1-10.6.2.2 UNI EN 12845)

The standards define the different possibilities of installing a pump intended to power a fire-fighting system in order of preference. Horizontal centrifugal pumps (End-suction) must be installed, if possible, negative suction head. The UNI EN 12845 standard clearly defines the parameters to define an negative suction head power supply:

  • at least two thirds of the effective capacity of the suction tank must be above the level of the pump shaft;
  • the pump shaft must not be more than 2 m above the minimum water level in the supply tank.
Gruppo antincendio sottobattente prestazioni

MF KDN BS | Positive suction head installation

(P.to 10.6.2.3-10.6.2.4 UNI EN 12845)

If negative suction head installation is not possible, the positive suction head system can be installed. The UNI EN 12845 standard indicates the maximum distance between the pump shafts and the lowest point of the suction pipe equal to 3.2 m. Furthermore, it is necessary to ensure the priming of the main pumps with a specific priming tank (1 for each main pump) positioned above them

Gruppo antincendio sottobattente prestazioni

Would you like more information on negative/positive suction head fire-fighting group  MF KDN BS?