FUNCTIONS AND ADVANTAGES
When the water network does not supply sufficient pressure and/or quantity of water, the MB CAPI pre-autoclave system, consisting of a pressure tank filled 2/3 of water and 1/3 of air and a pressurisation unit, is designed to guarantee the water supply to the highest floors of the buildings. The system guarantees maximum water hygiene, as it is drawn from a closed container under pressure with direct arrival from the water mains without coming into contact with the atmosphere before use.
If the network pressure is sufficient, the system remains stationary, avoiding waste of electricity and the water is renewed inside the tank, flowing towards the users. In this way the water never stagnates avoiding bacterial contamination. If the pressure is insufficient, the system intervenes with a constant flow of water to the electric pump(s) thanks to the inverter system, therefore the inlet pressure from the water mains accumulated in the tank combines with the pressure of the chosen pumping group. In this way it is possible to reduce the installed power and thus obtain economic savings.


DIMENSIONAL TABLE MajiBar MB CAPI*
| Model | Capacity (L) | Compressor (HP) | De | H | H1 | H2 | H3 | H4 | H5 | 1-8-10 | 2-3-2004 | 5-6-7-9 | 1v1 |
| MB CAPI 1-300 | 300 | 1 | 550 | 1554 | 135 | 445 | 745 | 845 | 1245 | 1″ 1/4 | 1″ 1/4 | 1/2″ | – |
| MB CAPI 1-500 | 500 | 1 | 650 | 1847 | 127 | 462 | 862 | 962 | 1512 | 1″ 1/4 | 1″ 1/2 | 1/2″ | 1″ |
| MB CAPI 1-750 | 750 | 1 | 750 | 2133 | 103 | 518 | 968 | 1068 | 1718 | 1″ 1/4 | 2″ | 1/2″ | 1″ |
| MB CAPI 1-1000 | 1000 | 1 | 850 | 2633 | 103 | 518 | 1168 | 1268 | 2218 | 1″ 1/4 | 2″ | 1/2″ | 1″ |
| MB CAPI 2-1500 | 1500 | 1 | 1,000 | 2295 | 105 | 600 | 1100 | 1200 | 1800 | 1″ 1/4 | 2″ | 1/2″ | 1″ |
| MB CAPI 2-2000 | 2000 | 1,5 | 1,000 | 2795 | 105 | 600 | 1250 | 1350 | 2300 | 1″ 1/4 | 2″ | 1/2″ | 1″ |
Pressurised tank technical drawing
| Num. Art | Discharge |
| 1 | Pressurised tank |
| 2-3-2004 | Power – Use |
| 5-9 | Visual level indicator |
| 6 | Pressure gauge |
| 8-11 | Level switch |
| 7 | Control instrument |
| 10 | Safety valve, anti-vacuum valve and automatic air supply |
Pre-autoclave system example layout
| Art. no. | Description |
| 1 | Pressurised tank |
| 2 | Pumping group |
| 3 | Belt driven compressor on base |
| 4 | Electrical panel for compressor control |
| 5 | Tank relief safety valve |
| 6 | Level switch to maintain air/water ratio (to be installed at 2/3 tank height) |
| 7 | Visual air/water level indicator inside the tank |
| 8 | Water network inlet with 2” ball valve |
| 9 | Tank discharge with 1” ball valve |
| 10 | Pressure booster pumping group delivery |
| 11 | Pressure gauge |
| 12 | Compressor pressure switch |